H3433 temperature and humidity regulator with RS485 output

H3433 temperature and humidity regulator with RS485 output

code: H3433
Humidistat, thermostat with two relay outputs. Outdoor, indoor use. Duct mount.

Relative humidity, temperature sensors at 150mm stem. Measured values are also converted to other humidity interpretation: dew point temperature, absolute humidity, specific humidity, mixing ratio, specific enthalpy. Three two-state inputs.

 

 Included in delivery: 

    • Traceable calibration certificate
    • Quick start manual
    • Free program TSensor for configuring of the transmitter is ready to Download
    • Free program SensorReader for logging values from one transmitter via RS485 to a PC disk file is ready to Download

 

 

   
Features Technical Data Download Optional accessories We recommend

Features

Humidistat is designed for two-state control of e.g. heating, ventilation, humidifier, dehumidifier, etc.
Transmitter is equipped with two relay outputs for alarm indication or control of external devices. Each relay can be assigned to any measured or computed value. For each relay setting of delay, hysteresis, audible alarm is enabled.
Measured temperature and relative humidity is recalculated to other humidity interpretations - dew point temperature, absolute humidity, specific humidity, mixing ratio or specific enthalpy.
Parameters are easy adjustable from regulator keyboard or from the computer. Large dual line LCD for simultaneous display of temperature, relative humidity or other calculated humidity interpretation is an advantage.
State-of-the-art capacitive polymer sensor ensures excellent calibration long term stability, inertia against water and condensation. Transmitter is designed for use in non-aggressive environment.

Transmitter is also equipped with three binary inputs for detection of two-state events - e.g. water, smoke, glass break detection, door contact.
 

HUMIDISTAT APPLICATIONS

- temperature and humidity control
- monitoring of temperature, humidity:

  • building management and automation
  • server rooms
  • telecommunication devices
  • warehouses, glasshouses
  • manufacturers
  • museums, archives, galleries
  • air-conditioned rooms, HVAC
  • weather stations

    Serial output RS485 is galvanically isolated from other circuitry to prevent collisions on the RS485 bus. The transmitter works with ModBus RTU communication protocol or with Advantech ADAM compatible protocol. Protocol is user selectable in special configuration mode by means of the PC. Serial link enables to read actual readings and modify transmitter configuration. Instrument works always in slave mode, i.e. responds only to master device query. Transmitters have the address space available from 1 to 255. Communication speed is 110 to 115200Bd.

     For acquiring values from several transmitters connected to RS485 bus, third party software is necessary to use.

    Tested functionality is with programs:

    LabVIEW from National Instruments, TIRS.NET, ControlWeb, EasyView.

Relative humidity range
 

Figure: Relative humidity operating range

Technical Data

Technical parameters Value
Output RS485
Measured Value Relative Humidity + Temperature
Construction Type Duct Mount (150mm)
Design Industrial
Temperature Measuring Range -30 to +125°C
Relay Output Yes
Two-State Input Yes
Lcd Display Yes
Maximum switching voltage, current, power of relay output 50V, 2A, 60VA
Audible alarm from built-in beeper - switchable
Relative humidity range 0 to 100%
Accuracy of relative humidity measurement ±2.5% relative humidity from 5 to 95% at 23°C
Accuracy of temperature output ±0.4°C from -30 to +100°C
±0.4% from reading over +100°C
Available temperature units degrees Celsius, Fahrenheit
Accuracy and range of dew point temperature output - for more details see graphs ±1.5°C at ambient temperature T<25°C and RH>30%
range -60 to +80 °C
Accuracy and range of absolute humidity output ±1.5g/m3 at ambient temperature T < 25°C
range 0 to 400 g/m3
Accuracy and range of specific humidity output ±2g/kg at ambient temperature T < 35°C
range 0 to 550 g/kg
Accuracy and range of mixing ratio output ±2g/kg at ambient temperature T < 35°C
range 0 to 995 g/kg
Accuracy and range of specific enthalpy output ±3kJ/kg at ambient temperature T < 25°C
range: 0 to 995 kJ/kg
Signal for binary inputs dry contact, open collector or two-state voltage signal.
Inputs are not galvanically isolated.
Minimum pulse length at binary input 500 ms
Voltage at open contact 3.3 V
Low voltage level 0 to +0.5 V
High voltage level +3.0 to +30V
Temperature operating range -30 to +80°C
Temperature operating range of LCD display readable to operating temperature +70°C, it is recommended to switch OFF the LCD over +70°C
Temperature compensation of the humidity sensor all temperature range
Filtering ability of sensor cover 0.025mm - filter with stainless steel mesh
Communication protocol ModBus RTU and Advantech ADAM compatible protocol
Communication speed 110 to 115200 Bd
IP protection IP65 electronics, IP40 sensors
Power 9-30Vdc, power consumption approximately 1W
Dimensions 136 x 293 x 45 mm (W x H x D), stem length 150 mm
Weight approximately 430g
Warranty 2 years

  size
doc Instruction Manual 2 MB
doc Quick Start Manual 810 kB
doc Datasheet 1.1 MB
doc Declaration of Conformity 30 kB
doc Description of communication protocols 420 kB

Program TSensor - free configuration program for transmitters and transducers, Code: TSensor more »
doc TSensor - free configuration program version 3.0.5.0 2.6 MB
doc TSensor - revision history 8 kB

Program SensorReader - free program for data read and store from one sensor, Code: SensorRead more »
doc SensorReader - free program for data recording from one sensor, version 2.0.1.0 1.3 MB

Optional accessories

H3431 temperature and humidity regulator with RS485 output
code: H3431
Humidistat, thermostat with two relay outputs. Outdoor, indoor use.