H3060 temperature and humidity regulator with 230Vac/8A relays
|
|
code: H3060 Humidistat, thermostat with two relay outputs. Outdoor, indoor use. Built-in humidity, temperature sensors. Measured values are also converted to other humidity interpretation: dew point temperature, absolute humidity, specific humidity, mixing ratio, specific enthalpy.
Included in delivery:
|
Features
Humidistat is designed for two-state control of e.g. heating, ventilation, humidifier, dehumidifier, etc.
Transmitter is equipped with two relay outputs for alarm indication or control of external devices. Each relay can be assigned to any measured or computed value. For each relay setting of delay, hysteresis, audible alarm is enabled.
Measured temperature and relative humidity is recalculated to other humidity interpretations - dew point temperature, absolute humidity, specific humidity, mixing ratio or specific enthalpy.
Parameters are easy adjustable from regulator keyboard or from the computer. Large dual line LCD for simultaneous display of temperature, relative humidity or other calculated humidity interpretation is an advantage.
State-of-the-art capacitive polymer sensor ensures excellent calibration long term stability, inertia against water and condensation. Transmitter is designed for use in non-aggressive environment.
HUMIDISTAT APPLICATIONS
- temperature and humidity control
- monitoring of temperature, humidity:
- building management and automation
- server rooms
- telecommunication devices
- warehouses, glasshouses
- manufacturers
- museums, archives, galleries
- air-conditioned rooms, HVAC
- weather stations
To set regulator easily by the user from the PC program buying of SP003 cable is necessary - see Optional accessory.
Free configuration program TSensor for regulator adjustment is ready to download anytime.
It is also enabled to adjust regulator from the instrument keyboard.
If different adjustment of relay outputs is required, please specify required output values (RH, T, Tdp, ..) in the order. Adjustment is free of charge.
Technical Data
| Technical parameters | Value |
|---|---|
| Output | None |
| Measured Value | Relative Humidity + Temperature |
| Construction Type | Ambient Air |
| Design | Industrial |
| Temperature Measuring Range | -30 to +80°C |
| Relay Output | Yes 230V |
| Two-State Input | No |
| Lcd Display | Yes |
| Maximum switching voltage, current of relay output | 250Vac, 8A |
| Audible alarm | from built-in beeper - switchable |
| Relative humidity range | 0 to 100% |
| Accuracy of relative humidity measurement | ±2.5% relative humidity from 5 to 95% at 23°C |
| Accuracy of temperature output | ±0.4°C |
| Available temperature units | degrees Celsius, Fahrenheit |
| Accuracy and range of dew point temperature output - for more details see graphs | ±1.5°C at ambient temperature T<25°C and RH>30% range -60 to +80 °C |
| Accuracy and range of absolute humidity output | ±1.5g/m3 at ambient temperature T < 25°C range 0 to 400 g/m3 |
| Accuracy and range of specific humidity output | ±2g/kg at ambient temperature T < 35°C range 0 to 550 g/kg |
| Accuracy and range of mixing ratio output | ±2g/kg at ambient temperature T < 35°C range 0 to 995 g/kg |
| Accuracy and range of specific enthalpy output | ±3kJ/kg at ambient temperature T < 25°C range: 0 to 995 kJ/kg |
| Temperature operating range | -30 to +80°C |
| Temperature operating range of LCD display | readable to operating temperature +70°C, it is recommended to switch OFF the LCD over +70°C |
| Temperature compensation of the humidity sensor | all temperature range |
| Filtering ability of sensor cover | 0.025mm - filter with stainless steel mesh |
| IP protection | IP65 electronics, IP40 sensors |
| Power | 110 to 240V / 50Hz to 60Hz |
| Current consumption | 230 VAC - max. 70 mA, 115 VAC - max. 120 mA |
| Dimensions | 136 x 214 x 45 mm (W x H x D), stem lenght 75mm |
| Weight | approximately 390g |
| Warranty | 2 years |
| size | |
|---|---|
Instruction Manual |
1.3 MB |
Quick Start Manual |
600 kB |
Datasheet |
1.1 MB |
Declaration of Conformity |
30 kB |
| Program TSensor - free configuration program for transmitters and transducers, Code: TSensor | more » |
|---|---|
TSensor - free configuration program version 3.0.5.0 |
2.6 MB |
TSensor - revision history |
8 kB |
Optional accessories
|
cable for transmitter adjustment via USB port
code: SP003
|
plastic sensor protection with stainless filter (gray)
code: F5200
|
PP4 Flat circular flange
code: PP4
|
|
PP90 Right-angled stainless steel flange
code: PP90
|
plastic gland for direct mounting of the humidity probe
code: SP004
|
Tool for easy connection to WAGO terminals 233 for serial output transmitters
code: SP006
|
|
Humidity Standard 10%RH, set 5pcs
code: HM023
|
Humidity Standard 80%RH, set 5pcs
code: HM024
|
Vessel for adjustment and calibration of humidity
code: MD046
|
|
H3061 temperature and humidity regulator with 230Vac/8A relays
code: H3061
Humidistat, thermostat with two relay outputs. Outdoor, indoor use. |
|
H3020 temperature and humidity regulator
code: H3020
Humidistat, thermostat with two relay outputs. Outdoor, indoor use. |


COMET SYSTEM, s.r.o.
Instruction Manual
TSensor - free configuration program version 3.0.5.0
TSensor - revision history










