COMET SYSTEM, s.r.o.
1.maje 1220
756 61  Roznov pod Radhostem
CZECH REPUBLIC
Tel.: +420 571 653 990
Fax: +420 571 653 993
E-mail: info@cometsystem.cz


 

Transmitters
And Regulators
Data
Loggers
Monitoring
Systems
Temperature
Recorder with Printer
Portable
Instruments
Temperature
Probes
Software

MS6D data logger

MS6D data logger

code: MS6D
The complete solution for monitoring of temperature, humidity and other values.

Included in delivery:

Data logger including the battery

  • Traceable calibration certificate. Calibration certificate contains calibration of 16 inputs 4-20mA, if it is not defined required configuration of inputs by the user. If required configuration of inputs is defined by the user, calibration certificate proves calibration of inputs in accordance with this required configuration - maximum one range for each of 16 inputs.
    Calibration of other ranges is optional.
  • USB communication cable
  • Basic manual
  • Free basic Windows software is ready to download at folder Download

 

   
Features Technical Data Download Optional accessories We recommend

Features

Applications:

  • Server rooms, data centers
  • Food and beverages industry (HACCP)
  • Pharmaceutical industry (GMP)
  • Blood stations, pharmacies
  • Horticulture and cultivation of plants
  • HVAC - heating, ventilation, air conditioning, cooling
  • Building and energy management
  • Building automation
  • Research and development
  • Laboratories (GLP) 

    Main advantage - user configurable inputs from PC program without any need to open the data logger unit. Each data logger contains 16 inputs for measurement and record of both analog and two-state values. Each input is individually configurable from user PC program to one from 17 measuring ranges.
    Also signals from sensors working on RS485 bus with ModBus or Advantech protocol can be recorded.
    Universal sixteen channel data logger is designed for data acquisition from sensors of variety values, alarm state indication, optionally for control of consecutive processes.
    Data is possible to download to the PC via USB, RS232, Ethernet interfaces or GSM modem for processing.
    Free program for monitoring system for Windows is ready to download.

    Data logger enables to:

    • Configure inputs for different input signal types from the PC program.
    • Individully configure each input channel for measurement, alarm evaluation and data logging , including individual logging interval for each input.
    • Individually program each input channel for different modes of record (continuous record, time dependent record, record only if specified logic conditions are matched, record triggered by external signal, etc.).
    • Set up to four different logic conditions for each channel to active alarm. Each condition compares measured values from inputs with set limits. It is possible to set hysteresis and delay of condition validity.
    • Indicate alarm state after matching defined combination up to four alarms from any inputs.
    • Activate selected relays depending on alarm states by means of output relays module.
    • Monitor online data by means of the Ethernet interface and Comet DBM program receiving SOAP messages.
    • Receive information from monitoring system by means of SMS messages via GSM modem - actual values, alarms, memory occupation etc.
    • Assign to each input channel name of actual recorded process to identify monitored object (e.g. type of monitored product). It is enabled to select this name from data logger keyboard during the operation.

    Each data logger input can be configured by the user from PC program depending on input signal character for measurement of dc current and voltage of different ranges, signals from RTD temperature sensors and thermocouples or dual-state signals with parameters in accordance with the table.
    Inputs are not galvanically isolated from each other.

Monitoring System Architecture

 

PARAMETERS OF CONFIGURABLE INPUTS
Measured value Accuracy Note
dc current
4 to 20 mA
±0.1% FS (±0.02mA) either from active source connected between COM and GND terminals or passive sensor connected between terminals +24V and COM
dc voltage
-10V to +10V
±0.1% FS
(±10 mV)
input resistance approximately 10 Mohms,
input terminals IN and COM
dc voltage
-1V to +1V
±0.1% FS
(±1 mV)
input resistance approximately 10 Mohms,
input terminals IN and COM
dc voltage
-100mV to +100mV
±0.1% FS
(±100 uV)
input resistance approximately 10 Mohms,
input terminals IN and COM
dc voltage
-18mV to +18mV
±0.1% FS
(±18 uV)
input resistance approximately 10 Mohms,
input terminals IN and COM
thermocouple K (NiCr-Ni)
-200 to +1300°C
±0.3% from reading + 1.5°C linearized, cold junction compensation,
input terminals IN and COM
thermocouple N
(NiCrSi-NiSiMg)
-200 to +1300°C
±0.3% from reading + 1.5°C linearized, cold junction compensation,
input terminals IN and COM
thermocouple J (Fe-Co)
-200 to +750°C
±0.3% from reading + 1.5°C linearized, cold junction compensation,
input terminals IN and COM
thermocouple S (Pt10%Rh-Pt)
0 to +1700°C
±0.3% from reading + 1.5°C linearized, cold junction compensation,
input terminals IN and COM
thermocouple B (Pt30%Rh-Pt)
+100 to +1800°C
±0.3% from reading + 1.0°C
from +300 to +1800°C
linearized,
without cold junction compensation,
input terminals IN and COM
thermocouple T (Cu-CuNi)
-200 to +400°C
±0.3% from reading + 1.5°C linearized, cold junction compensation,
input terminals IN and COM
Platinum temperature sensor Pt100
-200 to +600°C
±0.2°C
from -200 to +100°C
±0.2% from reading from +100 to +600°C
two-wire connection, measuring current approximately 0.8mA in pulse 50ms,
input terminals IN and COM
Platinum temperature sensor Pt1000
-200 to +600°C
±0.2°C
from -200 to +100°C
±0.2% from reading from +100 to +600°C
two-wire connection, measuring current approximately 0.5mA in pulse 50ms,
input terminals IN and COM
Nickel temperature sensor
Ni1000/6180ppm
-50 to +250°C
±0.2°C
from -50 to +100°C
±0.2% from reading from +100 to +250°C
two-wire connection, measuring current approximately 0.5mA in pulse 50ms,
input terminals IN and COM
two-wire measurement of resistance
0 to 300 Ohms
0.1% FS
(±0.3 Ohms)
measuring current approximately 0.8mA / 50ms,
input terminals IN and COM
two-wire measurement of resistance
0 to 3000 Ohms
0.1% FS
(±3 Ohms)
measuring current approximately 0.5mA / 50ms,
input terminals IN and COM
two-wire measurement of resistance
0 to 10000 Ohms
0.1% FS
(±10 Ohms)
measuring current approximately 0.1mA / 50ms,
input terminals IN and COM
Binary input for two-state signal input voltage for state "L" (IN-COM) < 0.8 V (Rin < 1 kOhm).
resistance of closed contact for state "L" (IN-COM) < 1 kOhm.
input voltage for state "H" (IN-COM) > 2 V.
resistance of closed contact for state "H" (IN-COM) > 10 kOhm.
minimum duration for sensing of change: 200ms.
RS485IN - input for serial signal RS485
- optionally
E.g. data acquisition from temperature, humidity, pressure sensors Tx41x, Hx43x.
input serves for reading from devices supporting protocol ModBus RTU or Advantech.
Connected to terminals next to terminals for channel 15 and 16.
Input can work with 16 devices.
Maximum speed 115200Bd.
Galvanically isolated.

                                                                                                                              OPTIONAL

Monitoring system input -  label Monitoring system inputs

Figure: data logger inputs with switch for selection of power voltage 12Vdc/24Vdc for connected sensors. Serial input RS485IN is optional.

                             

                               OPTIONAL

Figure: communication interface, alarm outputs, connection of power. Ethernet interface is optional.

 

Features of Ethernet interface:

Ethernet InterfaceEthernet interface  

Data logger is designed for  connection to standard computer network. The 10 and 100Mb/s Ethernet is supported.No need to build new data lines. Thanks this installation cost are essentially reduced and instant easy start of monitoring system operation is enabled. 

Modbus RTU  Modbus protocol

Enables to read actually measured values by means of industrial standard Modbus. Data is available in several formats. Protocol is suitable for implementing of MS data logger to SCADA system.

 

 
SNMPSNMPv1 protocol
Actually measured values can be acquired by means of SNMPv1 protocol. MIB tables are available for free.
Designed especially for IT applications and use in “managed” computer networks.

Fast data downloadFast data download

Record download speed was increased four-times from previous MS5 data logger generation. 

SOAP SOAP protocol 
Protocol designed for data logger integration to own www infrastructure. Available actual values can be captured by www server (Apache, IIS) and processed by the user.Communication protocol SOAP version 1.1. is supported. By means of this protocol data logger sends actual values in preset intervals to specified server.

SyslogSyslog protocol

Syslog message is sent after alarm state or data logger error appears. Syslog is compatible with RFC5424. 

EmailE-mail

Data logger sends warning emails up to three different addresses. E-mail is immediately sent after alarm state of monitored technological process appears. User is also informed on error states of device itself (measuring channel error, fulfilling of internal memory, self-test error).
SMTP servers requiring autentization are also supported.
 

 XML file  XML file

Actual values can be downloaded to XML file. This option is suitable for data logger integration to SCADA systems. 

  Display Data logger display  

Network parameters can be set directly from data logger display. It is possible to change IP address, subnetwork mask and initial gate.

 Secured web serverSecured WEB server

WWW server is built in the device. Here it is possible to monitor actual values, alarm states and information on data logger.Also access password for www pages can be entered. WWW pages are user modifiable. Free SDK description is available to create own www pages.

SNMP TrapSNMP Trap

SNMP Traps are sent after alarm state or device error appears. 

Database readyDatabase system

Prepared for connection to database system including online values transfer. 

 

Remote conditionsWWW remote conditions

Control of remote condition and relays is enabled also via www interface.

   
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
DIFFERENCES IN FEATURES OF DATA LOGGERS MS6D AND MS55D
Feature MS6D MS55D
Character of inputs: inputs configurable by the user from PC program fixed - depends of installed HW input modules
Maximum measured dc current: 20 mA dc 5 A dc
Maximum measured dc voltage: 10 V dc 75 V dc
Most sensitive measuring range of dc voltage: 18 mV dc 100 mV dc
Maximum measured ac voltage: - 50 V ac
Maximum measured ac current: - 5 A ac
Input for measurement of frequency: - 0 to 5 kHz
Input for counting of pulses: - yes
Possibility of galvanical isolation of inputs: only serial input RS485IN,
analog inputs cannot be isolated
yes
SMS port for sending/reception of SMS: included included
Dimensions including connectors: 215 x 225 x 44 mm 215 x 225 x 60 mm

Technical Data

Technical parameters Value
Total memory capacity 2MB (up to 480 000 values)
Memory type internal SRAM, backed-up by Lithium battery
Data logging modes noncyclic - logging stops after filling the memory
cyclic - after filling memory oldest data is overwritten by new
Data logging interval adjustable individually for all input channels from 1 second to 24 hours
Real time clock year, leap year, month, day, hour, minute, second, backed-up by Lithium battery
Resolution of the AD converter (analog channels) 16 bits, conversion duration approximately 60ms/channel
Communication speed 9600, 19200, 57600, 115200 Bd, 230400* Bd (* applicable for USB, Ethernet)
Power 24Vdc, consumption of data logger itself approximately 80 mA
Operating temperature range 0 to +50°C
Dimensions including connectors 215 x 225 x 44 mm (W x D x H)
Protection IP20
Weight approximately 800 g
Warranty 2 years

  size
doc Basic Instruction Manual 2.3 MB
doc Appendix to Instruction Manual 3.1 MB
doc Declaration of Conformity 30 kB
doc Datasheet 2.2 MB
doc Monitoring System setup wizard step by step - powerpoint presentation 4 MB
doc MIB tables 250 kB

Program for MS Data Loggers, Code: SWR006 more »
doc SWR006 Program for Data Loggers version 3.0.0.15 46.9 MB

DBM MS Logger Program - database software for MS data loggers, Code: DBM more »
doc DBM MS Logger Program version 3.0.0.17_II 99.6 MB

DBV Database Viewer for database programs DBL, DBM, DBS, Code: DBV more »
doc DBV Database Viewer 2.3.0.1 22.8 MB

Optional accessories

GD1250 thermocouple "K" wire probe 1m
code: GD1250-1/0
GD1250 thermocouple "K" wire probe 2m
code: GD1250-2/0
GD1250 thermocouple "K" wire probe 3m
code: GD1250-3/0
GD1250 thermocouple "K" wire probe 4m
code: GD1250-4/0
GD260 thermocouple "K" wire probe 1m
code: GD260-1/0
GD260 thermocouple "K" wire probe 2m
code: GD260-2/0
GD260 thermocouple "K" wire probe 3m
code: GD260-3/0
GD260 thermocouple "K" wire probe 4m
code: GD260-4/0
GD700 thermocouple "K" wire probe 1m
code: GD700-1/0
GD700 thermocouple "K" wire probe 2m
code: GD700-2/0
GD700 thermocouple "K" wire probe 3m
code: GD700-3/0
GD700 thermocouple "K" wire probe 4m
code: GD700-4/0
Pt1000TG8/0, cable 1 m
code: SN104
Pt1000TG8/0, cable 2 m
code: SN105
Pt1000TG8/0, cable 5 m
code: SN108
Pt1000TG8/0, cable 10 m
code: SN113
Pt1000TR050/0 1m Temperature probe
code: SN132
Pt1000TR050/0 2m Temperature probe
code: SN133
Pt1000TR050/0 5 m Temperature probe
code: SN136
Pt1000TR050/0 10 m Temperature probe
code: SN141
Pt1000TG7/0, cable 1 m
code: SN164
Pt1000TG7/0, cable 2 m
code: SN165
Pt1000TG7/0, cable 5 m
code: SN166
Pt1000TG7/0, cable 10 m
code: SN167
2301-220/0, cable 1 m
code: SN168
2021-150/0, cable 1 m
code: SN169
PTS350A-2/0, cable 2 m
code: SN170
2031-150/0 Temperature probe
code: SN175
2061-200/0 1m Temperature probe
code: SN178
2061-200/0 2m Temperature probe
code: SN179
2061-200/0 5m Temperature probe
code: SN180
2061-200/0 10m Temperature probe
code: SN181
PTS350A-5/0, cable 5 m
code: SN182
PTS350A-10/0, cable 10 m
code: SN183
Pt1000TGL40/0, cable 1 m
code: SN185
Pt1000TGL40/0, cable 2 m
code: SN186
Pt1000TGL40/0, cable 5 m
code: SN187
Pt1000TGL40/0, cable 10 m
code: SN188
Pt1000TR160/0, cable 1 m
code: SN199
Pt1000TR160/0, cable 2 m
code: SN200
Pt1000TR160/0, cable 5 m
code: SN201
Pt1000TR160/0, cable 10 m
code: SN202
Pt1000TR160/0, cable 15 m
code: SN203
Pt1000TR160/0, cable 20 m
code: SN204
PTS380K temperature sensor with a stainless steel connection head and connector
code: SN205
2091-200/0 Stick-in probe, cable 1m
code: SN210
2091-200/0 Stick-in probe, cable 2m
code: SN211
2091-200/0 Stick-in probe, cable 5m
code: SN212
2091-200/0 Stick-in probe, cable 10m
code: SN213
2071-030/0 Special probe with CINCH connector
code: SN214
Extension cable thermocouple K with female connector, 1meter length
code: SNP03/0
Extension cable thermocouple K with female connector,2meters
code: SNP06/0
Extension cable thermocouple K with female connector,3meters
code: SNP07/0
Extension cable thermocouple K with female connector,4meters
code: SNP08/0
Extension cable thermocouple K with female connector,5meters
code: SNP09/0
Extension cable thermocouple K with female connector,6meters
code: SNP10/0
Extension cable thermocouple K with female connector,7meters
code: SNP11/0
Extension cable thermocouple K with female connector,8meters
code: SNP12/0
Extension cable thermocouple K with female connector,9meters
code: SNP13/0
Extension cable thermocouple K with female connector,10meters
code: SNP14/0
Extension cable thermocouple K with female connector,11meters
code: SNP15/0
Extension cable thermocouple K with female connector,12meters
code: SNP16/0
Extension cable thermocouple K with female connector,13meters
code: SNP17/0
Extension cable thermocouple K with female connector,14meters
code: SNP18/0
Extension cable thermocouple K with female connector,15meters
code: SNP19/0
DBM MS Logger Program - database software for MS data loggers
code: DBM
Database program package.
DBV Database Viewer for database programs DBL, DBM, DBS
code: DBV
Low cost browser DBV Database Viewer enables several clients to view database from different places on network/internet.
Program for MS Data Loggers
code: SWR006
Program for Windows - comfort graphic environment data acquisition, including online graph, automatic data download, remote Display mode on Internet-Ethernet network, storing data on the network, administration of users and passwords.
MS6-Rack data logger
code: MS6-Rack
The complete solution for monitoring of temperature, humidity and other values. For mounting to 19" rack - one rack unit 1U. Enables to build in the optional MP016 output relays module with 16 relays - see Optional accessories.
MS6R data logger
code: MS6R
The complete solution for monitoring of temperature, humidity and other values. For desktop use with rubber feet - see Optional accessories. For mounting to 19" rack - one rack unit 1U.
MS55D data logger
code: MS55D
The complete solution for monitoring of temperature, humidity and other values.