COMET SYSTEM, s.r.o.
1.maje 1220
756 61  Roznov pod Radhostem
CZECH REPUBLIC
Tel.: +420 571 653 990
Fax: +420 571 653 993
E-mail: info@cometsystem.cz


 

Transmitters
And Regulators
Data
Loggers
Monitoring
Systems
Temperature
Recorder with Printer
Portable
Instruments
Temperature
Probes
Software

H0430 temperature transmitter and regulator with RS485 output

H0430 temperature transmitter and regulator with RS485 output

code: H0430
Ambient temperature transmitter with two relay outputs. Outdoor, indoor use.

Built-in temperature sensor.

Temperature transmitter is equipped with three two-state inputs for detection of  two-state signals - e.g. power presence, water, smoke, airflow, glass break detection, door contact.

Included in delivery: 

  • Traceable calibration certificate
  • Quick start manual
  • Free program TSensor for configuring of the transmitter is ready to Download
  • Free program SensorReader for logging values from one transmitter via RS485 to a PC disk file is ready to Download
   
Features Technical Data Download Optional accessories We recommend

Features

Temperature transmitter is designed for two-state control of e.g. heating, ventilation, humidifier, dehumidifier, etc.
Transmitter is equipped with two relay outputs for alarm indication or control of external devices. For each relay setting of delay, hysteresis, audible alarm is enabled.
Measured values are converted to galvanically isolated RS485 serial output.
Transmitter contains built-in temperature sensor.
Degrees Celsius and Fahrenheit are user selectable.
Parameters are easy adjustable from regulator keyboard or from the computer. Large dual line LCD display is an advantage.
Transmitter is also equipped with three binary inputs for detection of two-state events - e.g. water, smoke, glass break detection, door contact.
 

THERMOSTAT APPLICATIONS
- temperature control
- monitoring of temperature and three binary signals at:

  • building management and automation
  • server rooms
  • telecommunication devices
  • warehouses, glasshouses
  • manufacturers
  • museums, archives, galleries
  • air-conditioned rooms, HVAC

Serial output RS485 is galvanically isolated from other circuitry to prevent collisions on the RS485 bus. The transmitter works with ModBus RTU communication protocol or with Advantech ADAM compatible protocol. Protocol is user selectable in special configuration mode by means of the PC. Serial link enables to read actual readings and modify transmitter configuration. Instrument works always in slave mode, i.e. responds only to master device query. Transmitters have the address space available from 0 to 255. Communication speed is 110 to 115200Bd.

 

For acquiring values from several transmitters connected to RS485 bus, third party software is necessary to use.

Tested functionality is with programs:

LabVIEW from National Instruments, TIRS.NET, ControlWeb, EasyView.

Technical Data

Technical parameters Value
Output RS485
Measured Value Temperature
Construction Type Ambient Air
Design Industrial
Temperature Measuring Range -30 to +80°C
Relay Output Yes
Two-State Input Yes
Lcd Display Yes
Maximum switching voltage, current, power of relay output 50V, 2A, 60VA
Audible alarm from built-in beeper - switchable
Accuracy of temperature output ±0.4°C
Available temperature units degrees Celsius, Fahrenheit
Signal for binary inputs dry contact, open collector or two-state voltage signal.
Inputs are not galvanically isolated.
Minimum pulse length at binary input 500 ms
Voltage at open contact 3.3 V
Low voltage level 0 to +0.5 V
High voltage level +3.0 to +30V
Temperature operating range -30 to +80°C
Temperature operating range of LCD display readable to operating temperature +70°C, it is recommended to switch OFF the LCD over +70°C
Communication protocol ModBus RTU and Advantech ADAM compatible protocol
Communication speed 110 to 115200 Bd
IP protection IP65
Power 9-30Vdc, power consumption approximately 1W
Dimensions 136 x 191 x 45 mm (W x H x D), stem length 53 mm
Weight approximately 350g
Warranty 2 years

  size
doc Instruction Manual 2 MB
doc Quick Start Manual 810 kB
doc Datasheet 1.1 MB
doc Declaration of Conformity 30 kB
doc Description of communication protocols 420 kB

DBS Sensor Monitor - database program for data acquisition from Ethernet sensors P8xxx, Tx5xx, Hx5xx, Code: DBS more »
doc DBS Database Sensor Monitor version 2.3.0.1_II 55.2 MB

DBV Database Viewer for database programs DBL, DBM, DBS, Code: DBV more »
doc DBV Database Viewer 2.3.0.1 22.8 MB

Program TSensor - free configuration program for transmitters and transducers, Code: TSensor more »
doc TSensor - free configuration program version 3.0.5.0 2.6 MB
doc TSensor - revision history 8 kB

Program SensorReader - free program for data read and store from one sensor, Code: SensorRead more »
doc SensorReader - free program for data recording from one sensor, version 2.0.1.0 1.3 MB

Optional accessories

H3060 temperature and humidity regulator with 230Vac/8A relays
code: H3060
Humidistat, thermostat with two relay outputs. Outdoor, indoor use.
H0530 Temperature transmitter and regulator with Ethernet interface
code: H0530
Ambient temperature transmitter with two relay outputs.
H4331 Temperature transmitter with RS232 output
code: H4331
Temperature transmitter for Pt1000 sensor with two relay outputs. Outdoor, indoor use.
T0410 Temperature transmitter with RS485 output
code: T0410
Ambient temperature transmitter. Outdoor, indoor use.